Model:VITJ1.14/1250-10
Category:VI for contactors

| Main Technical Specification | ||
| VOLTAGE RATINGS | ||
| Rated voltage(Ur) | kV | 1.14 | 
| Rated short-time(1min)power-frequency withstand voltage(Ud) | kV | 21 | 
| Rated lightning impulse withstand voltage(Peak)(Up) | kV | 40 | 
| Rated frequency(fr) | Hz | 50 | 
| CURRENT RATINGS | ||
| Rated current(Ir) | A | 1250 | 
| Circuit resistance at lowest rated contact force | μΩ | ≤60 | 
| Rated short-time withstand current(lk) | kA | 10 | 
| Rated duration of short-circuit(tk) | s | 4 | 
| Rated peak withstand current(lp) | kA | 10 | 
| Rated making current | kA | 6.3 | 
| Limit breaking current | A | 10 | 
| MECHANICAL DATA | ||
| Weight of movable parts | kg | ≤0.6 | 
| Closing force due to bellow and atmosphere | N | 70±30 | 
| Force required to hold contacts open at full stroke | N | 120±40 | 
| MECHANICAL REQUIREMENTS | ||
| Clearance between open contacts | mm | 3±1 | 
| Average opening speed (average of first 75% contact gap) | m/s | 0.4-0.5 | 
| Average closing speed (average of last 30% contact gap) | m/s | 0.15-0.25 | 
| Rated added external contact final force | N | 250±50 | 
| Contact bouncing duration at closing operation | ms | ≤2 | 
| Closing and opening non-simultaneity of three-phase contacts | ms | ≤2 | 
| Maximum rebound during opening | mm | ≤1 | 
| LIFE | ||
| Storage life | years | 20 | 
| Rated mechanical endurance | Times | 300000 | 
| Contacts limit erosion | mm | 3 | 